Yueqing, Wenzhou, Zhejiang, China, 325604

JJTP1-63VAS Syn Asy Voltage Protector

The Three-Phase Voltage Current Relay Protector is a versatile and reliable solution for protecting your electrical systems. Designed for 63A, 60A, and 100A ratings at 220V, this protector offers adjustable over-voltage, under-voltage, and over-current protection. It also features three-phase unbalance and phase sequence protection to ensure system stability. With customizable active time and reconnect time, as well as the ability to manually calibrate voltage and current, this relay provides optimal protection for your equipment, making it an essential tool for any electrical setup.

其他信息

Item No.

JJTP1-63VAS

Warrenty

2 Years

Syn Asy Voltage Protector Parameters

Technical parameter setting range Factory setting Step Function description
Power-on delay time 1S-500S 10S 1S After external power cut,the time needed for power-on when power recovery.
Over-voltage protection value 230V-300V 270V 1V When the voltage of one phase is over the set value,the protector will cut off this phase and
switch to the next phase according to the sequence set in Pr1.When all three phases’voltage
is over the set value,the protector will cut off all lines
Over-voltage recovery value 225V-295V 265V / When the voltage is 5V or more than 5V lower than the over-voltage protection value,the
protector will automatically reset.This parameter automatically changes with the change of
over-voltage protection value and does not need to be set.
Under-voltage protection value 140V-210V 170V 1V When the voltage of one phase is under the set value,the protector will cut off this phase and
switch to the next phase according to the sequence set in Pr1.When all three phases’voltage
is under the set value,the protector will cut offall lines
Under-voltage recovery value 145V-215V 175V / When the voltage is 5V or more than 5V higher than the under-voltage protection value,the
protector will automatically reset.This parameter automatically changes with the change of
over-voltage protection value and does not need to be set.
Over-current protection value 3A-63A-OFF
3A-100A-OFF
40A
60A
1A When the current is higher than the set value,the protector will cut off the line.When setting
OFF,the protector will turn off over-current protection function.
Times of continuous over current
protection
OFF-1-20 OFF 1 When The times of continuous over-current protection exceeds the set value,the protector will
cut off the line,then it needs to be opened manually.
Phase sequence switching
detection time
OFF-1S-500S 10S 1S The time required to detect whether the voltage of the priority phase is stable before disconnect.
OFF means that there is no need to wait for detection and switch directly to the priority phase.
Phase sequence recovery
switching settings
ON ON-OFF / ON means that when the priority phase returns to normal,it will switch to the priority phase.
OFF means that even if the priority phase returns to normal,the protector will not switch to that
phase.
Phase sequence switching
recovery time
OFF-1S-500S 10S 1S Time required to switch to priority phase.
Over-current protection action
time
0.1S-30S 1.0S 0.1S When over current,the time needed for protection action.
Voltage calibration -9.5%-9.5% 0 0.5 Correct the voltage error.
Current calibration -9.5%-9.5% 0 0.5 Correct the current error.
Input phase priority selection ABC-ACB-
BAC-BCA-
CAB-CBA
ABC / Set theinput priority of each phase.
A:L1,B:L2,C:L3

Any special request? Welcome to tell Jiuji Electric right now!