The 63A/100A Electronic Type Automatic Changeover Switch is designed to provide reliable and uninterrupted power to essential single-phase loads by automatically selecting the optimal power supply. It features over-voltage and under-voltage protection, along with a voltage display for monitoring. The switch ensures a seamless transition between power sources when one becomes faulty or experiences voltage irregularities, cutting off power instantaneously to protect electrical equipment. Additionally, the priority power supply can be set, and the switch will revert to it once normal voltage is restored.
Item No. | JJTP2-63V |
---|---|
Warrenty | 2 Years |
Technical parameter | setting range | Factory setting | Step | Function description | |||||||
Power-on delay time | 1S-500S | 10S | 1S | After external power cut,the time needed for power-on when power recovery. |
|||||||
Over-voltage protection value | 230V-300V | 270V | 1V | When the voltage is higher than the set value,the protector willcut off the line. |
|||||||
Over-voltage recovery value | 225V-295V | 265V | 1 | When the voltage is 5V or more than 5V lower than the over-voltage protection value,the protector will automatically reset. |
|||||||
Under-voltage protection value | 140V-210V | 170V | 1V | When the voltage is lower the set value,the protector will cut off the line. |
|||||||
Under-voltage recovery value | 145V-215V | 175V | 1 | When the voltage is 5V or more than 5V highe than the under-voltage protection value,the protector will automatically reset. |
|||||||
Recovery delay time | 1S-500S | 10S | 1S | After voltage recovery,the time needed for automatic reset. |
|||||||
Protection action time | 1 | 1.0S | / | When over or under voltage,the time needed for protection action. |
|||||||
Voltage calibration | -9.5%-9.5% | -2.0 | 0.5 | Correct the voltage error. | |||||||
Input phase priority selection | ABC-ACB- BAC-BCA- CAB-CBA |
ABC | / | Set the input priority of each phase. A:L1,B:L2,C:L3 |